Example of Over Current Protection Setting using DIgSILENT PowerFactory

Collapse
X
 
  • Filter
  • Time
  • Show
Clear All
new posts

  • Example of Over Current Protection Setting using DIgSILENT PowerFactory

    This exercise shows how the PF can be used to calculate fault currents and set an overcurrent relay. The coordination graphs will be shown and tripping calculations will be displayed.

    Click image for larger version

Name:	Fig00.png
Views:	1
Size:	35.2 KB
ID:	669
    Last edited by ; 09-04-2010, 09:34 PM.

  • #2
    Modelling of the network using PowerFactory

    The first setp is to model the network. This is done by creating a new project.

    Click image for larger version

Name:	Fig01.png
Views:	1
Size:	4.6 KB
ID:	537
    Last edited by ; 09-04-2010, 09:36 PM.

    Comment


    • #3
      Calculation of Maximum and Minimum Fault Currents

      As known from basic power system theory that the maximum fault current occurs at network when we have three phase fault.
      The figure below shows the result when parameters are defined in the PwerFactory model.

      The maximum fault current = 875 A as expected.

      Click image for larger version

Name:	Fig02.png
Views:	1
Size:	7.3 KB
ID:	539

      The minimum fault current = 758 A as expected

      Click image for larger version

Name:	Fig03.png
Views:	1
Size:	7.6 KB
ID:	538
      Last edited by ; 09-04-2010, 09:37 PM.

      Comment


      • #4
        The next step is to define the protection relay.

        Right click below the transformer and select New Devices -----> Relay Model

        Click image for larger version

Name:	Fig04.png
Views:	1
Size:	9.2 KB
ID:	541

        At Relay Type click Select Global Type

        Click image for larger version

Name:	Fig05.png
Views:	1
Size:	55.1 KB
ID:	540

        This will take you to library as shown in figure below.
        Choose the following relay as an example in this exercise.
        Other relays can be used if desirable.

        Library ----> Relays ----> Relays ---->
        select then Overcurrent Relays ----> GE Alstom ----> MCGG Series ----> MCGG-22.

        Click image for larger version

Name:	Fig06.png
Views:	1
Size:	57.5 KB
ID:	542
        Last edited by ; 09-04-2010, 09:40 PM.

        Comment


        • #5
          Now it is time to define the CT for this relay
          Click on Create CT as shown below

          Click image for larger version

Name:	Fig07.png
Views:	1
Size:	42.9 KB
ID:	544

          Then choose currnet ratio ----> write 800 A in primary. Click OK

          Click image for larger version

Name:	Fig08.png
Views:	1
Size:	100.9 KB
ID:	543
          Last edited by ; 09-04-2010, 09:31 PM.

          Comment


          • #6
            Now we need to display the rely using colour.
            Click on colour map as shown below.

            Click image for larger version

Name:	Fig09.png
Views:	1
Size:	8.6 KB
ID:	547

            Then from drop down menu select
            Relays, Current and Voltage Transformers as shown

            Click image for larger version

Name:	Fig10.png
Views:	1
Size:	45.0 KB
ID:	546

            When you click OK, the SLD shows now the line in Red where relay is connected.

            Click image for larger version

Name:	Fig11.png
Views:	1
Size:	4.6 KB
ID:	545

            Comment


            • #7
              We need now to create the graph for the protection devices.

              Right click on the SLD where the relay is connected as sown below.
              Then select Create Time-Overcurrent Plot.

              Click image for larger version

Name:	Fig12.png
Views:	1
Size:	11.2 KB
ID:	550

              The log graph appears as another sheet as shown below.

              Click image for larger version

Name:	Fig13.png
Views:	1
Size:	14.6 KB
ID:	549

              We can also click right on the graph and add the Transformer Damage Curve as shown.

              Click image for larger version

Name:	Fig14.png
Views:	1
Size:	20.3 KB
ID:	548

              Colour of Transformer Damage Curve can be chosen as shown below.

              Click image for larger version

Name:	Fig15.png
Views:	1
Size:	95.6 KB
ID:	553

              We can also select the voltage base for displaying the graphs, as shown below.

              Click image for larger version

Name:	Fig16.png
Views:	1
Size:	100.3 KB
ID:	551

              There is also of course option to display the fault current (875 A) in different colour (blue)
              and also the tripping time of relay (1.357 s) for that fault current.

              Click image for larger version

Name:	Fig17.png
Views:	1
Size:	14.1 KB
ID:	552

              Comment


              • #8
                Re: Example of Over Current Protection Setting using DIgSILENT PowerFactory

                Thank you for this topic

                Comment