Announcement
Collapse
No announcement yet.
Example of Over Current Protection Setting using DIgSILENT PowerFactory
Collapse
X
-
Example of Over Current Protection Setting using DIgSILENT PowerFactory
-
Calculation of Maximum and Minimum Fault Currents
As known from basic power system theory that the maximum fault current occurs at network when we have three phase fault.
The figure below shows the result when parameters are defined in the PwerFactory model.
The maximum fault current = 875 A as expected.
The minimum fault current = 758 A as expected
Comment
-
The next step is to define the protection relay.
Right click below the transformer and select New Devices -----> Relay Model
At Relay Type click Select Global Type
This will take you to library as shown in figure below.
Choose the following relay as an example in this exercise.
Other relays can be used if desirable.
Library ----> Relays ----> Relays ---->
select then Overcurrent Relays ----> GE Alstom ----> MCGG Series ----> MCGG-22.
Comment
-
We need now to create the graph for the protection devices.
Right click on the SLD where the relay is connected as sown below.
Then select Create Time-Overcurrent Plot.
The log graph appears as another sheet as shown below.
We can also click right on the graph and add the Transformer Damage Curve as shown.
Colour of Transformer Damage Curve can be chosen as shown below.
We can also select the voltage base for displaying the graphs, as shown below.
There is also of course option to display the fault current (875 A) in different colour (blue)
and also the tripping time of relay (1.357 s) for that fault current.
Comment
Comment